Skip to contentLBT Power builds dual source load bank systems for data center commissioning teams that need to test two independent power sources without using two separate load banks. Source A and Source B can be loaded, monitored, and reported from one cabinet.
Use it as a compact data center load bank for A/B feed validation, UPS redundancy testing, dual-feeder PDU commissioning, and L4/L5 integrated systems testing.
A dual source load bank is a load testing system with two independent input channels for testing redundant power paths. Instead of moving one load bank between Source A and Source B, commissioning teams can apply controlled load to both feeds from one enclosure.
For data centers, this helps simulate dual-corded IT equipment and validate UPS paths, PDU feeders, STS/ATS transfer behavior, voltage dip, source balance, and load continuity before live servers are connected.
Modern data centers use dual UPS systems, A/B rack feeds, redundant PDUs, STS/ATS switching, and backup generator paths. Testing one feed at a time may prove the equipment individually, but it can miss interaction problems under real commissioning conditions.
A dual source load bank helps commissioning teams verify both paths with controlled, repeatable electrical load. That makes it easier to capture per-source measurements, compare A and B paths, and prove redundancy before the facility goes live.
Testing Source A and Source B separately can miss transfer response, load sharing, source imbalance, and thermal behavior when both paths are active.
Two standard load banks mean more transport, more cabling, more calibration records, more operators, and more floor space.
A common load may show total kW, but it does not always give clean per-source records for UPS and PDU balance verification.
Commissioning teams need voltage, current, kW, temperature, transfer timing, and alarm records that can be attached to handover reports.
Confirm voltage, phase, frequency, target load, breaker rating, cable route, and whether the test is UPS, PDU, STS/ATS, or generator focused.
Connect Source A and Source B to isolated channels according to the approved method of procedure and safety boundary.
Apply planned load steps to one channel, both channels, or transfer scenarios while recording voltage, current, power, temperature, and alarms.
Run STS/ATS or UPS failover sequences and confirm load continuity, transfer timing, voltage dip, recovery behavior, and alarm response.
Use per-channel data to support commissioning reports, deficiency tracking, owner witness testing, and final sign-off.
| Parameter | Two Standard Load Banks | LBT Power Dual Source Load Bank |
|---|---|---|
| Enclosure count | 2 | 1 |
| Floor footprint | Two separate units | One compact cabinet |
| Cable runs | Separate routing per unit | Organized Source A / Source B routing |
| Control interface | Two panels or controllers | One HMI for both channels |
| Simultaneous test | More operator coordination | Single-operator coordinated test |
| Per-channel data logging | Manual data merge required | Time-aligned Source A / Source B records |
| Commissioning report | Separate files | Cleaner source comparison |
| Transport and rigging | Two shipments or rentals | One configured shipment |
Verify UPS redundancy, bypass transfer, output stability, and load continuity under controlled load.
Confirm each PDU feeder can carry design load and that A/B paths remain balanced during staged testing.
Simulate transfer between normal and alternate sources while tracking voltage dip, continuity, and event timing.
Each dual source load bank is configured from the project schedule, source rating, feeder arrangement, reporting requirements, and site constraints. Power, voltage, cooling method, enclosure rating, and communication protocol are confirmed before production.
Typical options are listed below. Final specifications are confirmed before quotation.
| Parameter | Range / Option |
|---|---|
| Rated power range | 21-51 kW standard range; project-specific options on request |
| Channel design | Two electrically isolated input channels with project-specific load distribution |
| Voltage range (AC) | 380 V - 690 V, 50/60 Hz |
| Voltage range (DC) | 24 V - 1,000 V |
| Cooling | Forced air or liquid-cooled configuration |
| Enclosure rating | Indoor or outdoor enclosure according to site requirement |
| Control | Local HMI with optional remote communication |
| Data logging | Per-channel voltage, current, power, temperature, and event record export |
| Documentation | FAT records, wiring drawings, user manual, and compliance documents on request |
Share source A/B voltage, load range, test scenario, site condition, and schedule. We confirm the configuration before quotation.
Our engineers create electrical and mechanical drawings for review before manufacturing starts.
The load bank is assembled with project-specific wiring, channel design, control logic, and enclosure configuration.
FAT can document voltage, current, power, temperature, switching timing, and channel operation before shipment.
Global shipping with protective crating. Site commissioning support is available for projects that need supervision or operator training.
Custom load bank engineering and factory testing before shipment.
Documentation can include drawings, FAT records, user manuals, and project-specific test records.
It is used to test two independent power sources, such as UPS A/B paths, PDU dual feeders, STS/ATS transfer sources, or generator feeders, under controlled electrical load.
No. Two standard units can test two sources, but a dual source load bank provides a single configured cabinet, coordinated control, organized cabling, and cleaner per-source records for commissioning.
Yes. It is especially useful for data center A/B power path testing, UPS failover testing, PDU commissioning, STS/ATS transfer tests, and redundancy validation.
Send Source A/B voltage, AC or DC requirement, target kW, test scenario, load steps, test duration, indoor/outdoor condition, and reporting requirements.
Yes. FAT records, wiring drawings, operation manuals, and project-specific documentation can be prepared according to the confirmed configuration.
Plan load bank testing for data center power, cooling, UPS, PDU, generator, and commissioning systems.
View data center load bank testing solutionReview UPS load bank testing procedures for backup power, battery runtime, transfer stability, and commissioning.
View UPS load bank testing guideTest generator load pickup, stability, wet stacking prevention, and backup power readiness under controlled load.
View generator load bank testingUse containerized load banks for higher-capacity data center, generator, UPS, and outdoor commissioning tests.
View container load bank optionsUse the checklist to plan L5 testing, PDU commissioning, heat load testing, CDU validation, and load bank setup.
View commissioning checklistSend source A/B voltage, target load, test duration, site condition, and reporting requirements for a configuration review.
Request a dual source load bank quoteTell us your Source A/B voltage, target load, test scenario, site environment, and required report format. We will review the application and return a practical technical proposal.
We use necessary cookies and optional analytics cookies. See our Cookie Policy.
LBT Power designs and manufactures high-performance load banks, supporting sample and small-batch customization to meet unique testing requirements for global projects.
Copyright 2026 LBT Loadbanks Co., Ltd. All Rights Reserved. | Company Information | Privacy Policy | Cookie Policy | Terms | Warranty | Quality & Compliance