Bidirvolt Custom Rack Load Bank

Bidirvolt Rack-Mounted Liquid-Cooled Load Bank Specs and Custom Options

This page summarises the standard configuration and common engineering customisation options for rack-mounted liquid-cooled load banks used in CDU testing, AI rack commissioning, server heat load simulation, and data center acceptance testing.

A standard rack-mounted liquid-cooled load bank is usually enough for 19-inch rack commissioning. Large AI data center projects often need deeper customisation because rack power, cold plate resistance, UQD connectors, coolant, and control software vary from site to site.

Quick answer: standard Bidirvolt rack-mounted liquid-cooled load banks can cover rack form factor, power, voltage, coolant, pressure, UQD connectors, sensors, Modbus communication, and safety protection. Custom projects can add non-standard rack dimensions, higher power density, adjustable hydraulic resistance, special quick connectors, transient load modules, and central control software.
Rack-mounted liquid-cooled load bank installed in an IT rack with folded open front access
Rack installation view for load bank fit, clearance, and deployment planning.
Front view of a rack-mounted liquid-cooled load bank with control panel and indicators
Front panel view for controls, indicators, mounting points, and operator access.
Rear three-quarter view of a rack-mounted liquid-cooled load bank showing coolant and power interfaces
Rear interface view for coolant connectors, power input, and project customisation.

Standard Rack-Mounted Load Bank Configuration

For normal data center acceptance testing, the standard configuration should first match the rack, the PDU, and the CDU secondary loop. Bidirvolt can configure units around the project voltage, rack U height, connector type, coolant, and commissioning records.

CategoryParameterTypical Standard Range
PhysicalForm factor and weight19-inch rack-mounted, 2U / 3U / 4U, usually around 25-45 kg depending on configuration
PowerRated power and voltage10kW, 20kW, 30kW, or 40kW per unit; AC 380V / 400V / 415V / 480V, 50/60Hz
Load controlStep control and accuracy0.5kW or 1kW step control, with project-specific accuracy requirement
Cooling loopCoolant, pressure, delta-T, and pressure dropDeionised water, pure water, PG25/PG50 glycol mixture; 1.0 MPa working pressure; 10-15 degrees C design delta-T; adjustable pressure drop where required
InterfaceQuick connectors and sensorsUQD02 / UQD04 or project-specific non-drip connectors; inlet/outlet temperature, pressure, differential pressure, and flow monitoring
CommunicationControl protocol and reportingRS485 Modbus RTU, Ethernet Modbus TCP, SNMP, trend curves, and report export

When Do You Need a Custom Rack-Mounted Unit?

Customisation becomes important when the load bank must represent a specific AI rack instead of a generic server rack. Projects based on very high rack density, OCP-style frames, non-standard manifolds, or special coolant may require a custom rack-mounted liquid-cooled load bank rather than a standard model.

Typical triggers include 21-inch rack requirements, unusual rear clearance, special mounting ears or sliding rails, 50kW+ power in a compact module, or rack-level heat loads above 100kW. These are good reasons to send drawings and CDU data before requesting a quote.

Hydraulic Customisation for CDU and Manifold Testing

The most important custom option is often water-side behaviour. A load bank for serious CDU validation should not only generate heat; it should also simulate the pressure-flow behaviour of server cold plates.

  • Adjustable hydraulic resistance: manual or motorised needle valves can help simulate different cold plate P-Q curves.
  • Connector adaptation: Parker, Staubli, Danfoss, UQD, DN10, DN15, or other project-specific quick connectors can be considered.
  • Coolant compatibility: sealing and wetted materials can be selected for glycol mixtures, deionised water, pure water, or special liquid cooling media.
  • Manifold balance testing: adjustable flow resistance helps reveal branch bias, low-flow paths, and pump head limitations.

Electrical, Transient Load, and Control Customisation

Electrical customisation may include North American 480V input, project-specific three-phase layouts, HVDC input, solid-state switching, or faster transient load response. A transient load module can help simulate sudden AI training load changes and observe CDU pump and valve response.

For larger deployments, control software is often as important as hardware. Bidirvolt can discuss group control, Modbus point mapping, central PC software, test scripts, trend curves, and report export. For broader engineering scope, see the custom load bank engineering page and custom load bank software options.

RFQ Information to Send Bidirvolt

To quote a custom rack-mounted liquid-cooled load bank accurately, prepare the main site parameters first. A short but complete RFQ saves several rounds of technical clarification.

  • Target power per unit and total rack heat load.
  • Rack type, U height, depth, rear clearance, mounting rail, and any lifting or caster requirements.
  • Site voltage, phase, frequency, PDU capacity, and breaker rating.
  • Coolant type, flow rate, pressure rating, design delta-T, and target pressure drop.
  • UQD or quick connector model, hose direction, and manifold drawing if available.
  • Communication protocol, BMS/DCIM interface, group control requirement, and report export format.

Request a Custom Rack-Mounted Liquid-Cooled Load Bank Quote

Bidirvolt can configure rack-mounted liquid-cooled load banks around your CDU, rack manifold, UQD connectors, voltage, coolant, pressure rating, control protocol, and data center commissioning workflow.

Send your rack drawings, CDU flow data, connector model, site voltage, and test report requirements through the Bidirvolt contact page.

Request a Custom Quote